Skip to content

Wire Gauge Calculator

Free wire gauge calculator for AWG sizing, ampacity lookup, and voltage drop analysis. Enter your circuit amperage and distance to find the correct copper or aluminum wire gauge per NEC standards.

Loading calculator

Preparing Wire Gauge Calculator...

Reviewed & Methodology

Every calculator is built using industry-standard formulas, validated against authoritative sources, and reviewed by a credentialed financial professional. All calculations run privately in your browser - no data is stored or shared.

Last reviewed:

Reviewed by:

Written by:

How to Use the Wire Gauge Calculator

  1. 1. Enter circuit amperage - input the maximum current the circuit will carry.
  2. 2. Select conductor material - choose copper or aluminum (aluminum requires larger gauge for the same amperage).
  3. 3. Enter wire run distance - input the one-way distance in feet from the panel to the load.
  4. 4. Set system voltage - select 120V, 208V, 240V, or 480V for your circuit.
  5. 5. Review results - see the recommended AWG gauge, ampacity rating, voltage drop percentage, and wire resistance per 1,000 feet.

Wire Gauge Calculator

This wire gauge calculator determines the correct AWG wire size based on circuit amperage, conductor material, run distance, and system voltage. Enter your circuit parameters to get the NEC-rated wire gauge, ampacity rating, and voltage drop percentage — so your installation stays both safe and code-compliant.

How Wire Gauge Is Calculated

Wire sizing follows two steps. First, the calculator matches your circuit amperage to the smallest AWG gauge whose NEC Table 310.16 ampacity (at 75 degrees C) meets or exceeds that load. Second, it verifies voltage drop using:

Voltage Drop (%) = (2 x Distance (ft) x Current (A) x Wire Resistance (ohm/1000 ft)) / (1000 x System Voltage) x 100

If the voltage drop exceeds 3% — the NEC-recommended maximum for branch circuits — the calculator steps up one gauge size and recalculates. For aluminum conductors, the resistance values are approximately 61% higher than copper at the same AWG, so the calculator substitutes the correct aluminum resistance table automatically.

Example: a 20A circuit running 75 feet on 12 AWG copper at 120V: VD = (2 x 75 x 20 x 1.98) / (1000 x 120) x 100 = 4.95%

That exceeds 3%, so the calculator recommends upsizing to 10 AWG (resistance 1.24 ohm/1000 ft), which drops the voltage drop to 3.1% — just inside the limit.

Worked Examples

Scenario 1 — Bedroom lighting circuit (15A, 50 ft, 120V copper)

  • Required ampacity: 15A — 14 AWG (15A rated) qualifies
  • VD = (2 x 50 x 15 x 3.14) / (1000 x 120) x 100 = 3.93% — exceeds 3%
  • Upsize to 12 AWG: VD = (2 x 50 x 15 x 1.98) / 120,000 x 100 = 2.48% — pass
  • Result: 12 AWG copper

Scenario 2 — Electric dryer (30A, 30 ft, 240V copper)

  • Required ampacity: 30A — 10 AWG (30A rated) qualifies
  • VD = (2 x 30 x 30 x 1.24) / (1000 x 240) x 100 = 0.93% — well under 3%
  • Result: 10 AWG copper, no upsize needed

Scenario 3 — Sub-panel feeder (100A, 150 ft, 240V aluminum)

  • Required ampacity: 100A — 1/0 AWG aluminum (100A rated) qualifies
  • Aluminum resistance for 1/0 AWG: 0.190 ohm/1000 ft
  • VD = (2 x 150 x 100 x 0.190) / (1000 x 240) x 100 = 2.38% — pass
  • Result: 1/0 AWG aluminum

AWG Reference Table

AWGDiameter (mm)Cu Ampacity (75 C)Al Ampacity (75 C)Cu Resistance (ohm/1000 ft)Common Use
141.6315A3.14Lighting circuits
122.0520A1.98General receptacles
102.5930A1.24Dryers, AC units
83.2650A40A0.778Ranges, water heaters
64.1165A50A0.491Large appliances
45.1985A65A0.308Sub-panels, feeders
26.54115A90A0.194Service entrance
1/08.25150A120A0.122Large feeders
2/09.27175A135A0.0967200A service
4/011.68230A180A0.0608Main service entrance

When to Use This Calculator

  • Sizing a new branch circuit for a kitchen appliance, EV charger, or workshop tool
  • Checking whether an existing wire run has acceptable voltage drop before adding load
  • Selecting feeder conductors for a detached garage, outbuilding, or sub-panel
  • Comparing copper versus aluminum costs on larger feeder runs (100A and above)
  • Verifying that conduit fill and conductor count derating are accounted for before inspections

Common Mistakes

  1. Ignoring voltage drop on long runs. A 12 AWG wire is rated for 20A, but a 100-foot run at 20A on 120V drops 4.1% — above the NEC 3% guideline. Always check the actual drop, not just the ampacity.
  2. Using copper ampacity tables for aluminum wire. Aluminum carries less current for the same gauge. Substituting 6 AWG aluminum (50A) where 6 AWG copper (65A) was specified leaves the circuit under-rated and may create a fire hazard.
  3. Forgetting conductor count derating. Running six current-carrying conductors in one conduit requires 80% derating per NEC 310.15(C)(1). A 12 AWG wire rated at 20A must be derated to 16A — possibly requiring an upsize.
  4. Skipping anti-oxidant compound on aluminum terminations. Aluminum forms an oxide layer that increases resistance at connections, causing heat buildup. Always apply listed anti-oxidant compound and use AL/CU-rated connectors.

Real-World Applications

Wire gauge selection appears wherever electrical circuits are installed or inspected. Residential electricians use it daily to size branch circuits for kitchens (20A small appliance circuits on 12 AWG), bathrooms (20A GFCI circuits), and dedicated appliance loads like 30A dryer circuits (10 AWG) and 50A ranges (8 AWG). Commercial electricians use voltage drop calculations to size feeder conductors for panels located far from the utility transformer — a 480V three-phase feeder running 300 feet to a motor control center might jump from 2 AWG to 1/0 AWG purely to keep voltage drop below 2%. Solar installers rely on the same formulas to size DC home-run cables from rooftop arrays to inverters, where every fraction of a percent of voltage drop reduces system output. Building inspectors use ampacity tables to verify that the installed wire matches the breaker size on every branch circuit.

Tips

  1. Always match wire gauge to the breaker size first — a 20A breaker on 14 AWG wire is a code violation regardless of actual load
  2. For runs over 100 feet on 120V circuits, plan for 10 AWG from the start to avoid voltage drop issues without rewiring later
  3. Use UF-B (direct burial) cable or THWN in conduit for underground runs — standard NM-B (Romex) is not rated for wet or underground locations
  4. When switching to aluminum on feeders, upsize two AWG numbers: use 2 AWG aluminum where 4 AWG copper would be specified for 70A circuits
  5. Leave 12-18 inch service loops at every panel and junction box — they allow re-termination if a connection fails and add no meaningful resistance
  6. Derate ampacity by 80% for more than three current-carrying conductors in a conduit — always verify the final derated value exceeds your circuit load before finalizing gauge selection

Frequently Asked Questions

How does the AWG (American Wire Gauge) system work?
AWG is an inversely numbered system -- lower numbers mean thicker wire. AWG 14 (1.63 mm diameter) is the thinnest wire allowed for 15A residential circuits, while AWG 4/0 (0000, 11.68 mm) handles 195A. Each decrease of 3 AWG numbers approximately doubles the cross-sectional area and ampacity. For example, 12 AWG handles 20A, 9 AWG handles about 40A, and 6 AWG handles 55A.
What is the ampacity of common wire gauges?
Per NEC Table 310.16 at 75 degrees C: 14 AWG = 15A, 12 AWG = 20A, 10 AWG = 30A, 8 AWG = 40A, 6 AWG = 55A, 4 AWG = 70A, 3 AWG = 85A, 2 AWG = 95A, 1 AWG = 110A, 1/0 AWG = 125A, 2/0 AWG = 145A, 3/0 AWG = 165A, and 4/0 AWG = 195A. These ratings apply to copper conductors with 75 degree C insulation (THWN-2) in conduit with no more than three current-carrying conductors.
How do I calculate voltage drop for a wire run?
Voltage drop is calculated as VD = (2 x L x I x R) / 1000, where L is one-way distance in feet, I is current in amps, and R is the wire resistance per 1,000 feet (e.g., 1.98 ohms for 14 AWG copper, 1.24 ohms for 12 AWG). The NEC recommends keeping branch circuit voltage drop below 3% and total (feeder + branch) below 5%. If the calculated drop exceeds 3%, upsize the wire gauge.
When should I use copper wire versus aluminum wire?
Copper has about 61% the resistance of aluminum and is standard for branch circuits (14-10 AWG). Aluminum is cheaper per ampere and commonly used for service entrance cables (4/0 AWG and larger) and feeder conductors. When substituting aluminum for copper, upsize by two AWG numbers (e.g., use 2 AWG aluminum instead of 4 AWG copper for 70A). Always use anti-oxidant compound and AL/CU-rated connectors with aluminum wire.
What is conduit fill and how does it affect wire sizing?
NEC Chapter 9 limits conduit fill to 40% of the conduit's cross-sectional area for three or more conductors. Overfilling prevents heat dissipation and makes pulling wire difficult. For example, three 12 AWG THHN wires (0.0133 sq in each) total 0.0399 sq in, requiring at least 1/2-inch EMT conduit (0.122 sq in usable area at 40% fill). Additionally, when more than three current-carrying conductors share a conduit, ampacity must be derated per NEC Table 310.15(C)(1).
Calculators